The HVAC equipment will start in stage 1. Options are Auto and 10-180 minutes. This option should also be used for installation where the heat pump evaporator coil is downstream from the source of auxiliary heat. It will then automatically start the system at that stage (ie if it calculates that it will take 15 minutes at stage 2 but only 7 minutes at stage 3, the system will immediately turn on stage 2 to meet the set point). Heat Stages:  Allows you to configure up to 3 stages of heat. If your compressor is engaged and then the call is immediately cancelled, the compressor will continue running for this set value (5 minutes) before turning off. As the stage 1 temperature delta is exceeded, the second stage will engage. This ensures the compressor does not short cycle (which could affect the operating life of the system). This time is adjustable from 240–900 seconds. Select Compressor Min Cycle Off Time; select 600 seconds. You can press Back to go back and make any changes. Furnace Type:  Allows you to configure the type of furnace connected. This feature allows you to view the terminal connections of the equipment interface as determined by the configuration options selected during the installation process. If this option is enabled, the thermostat will cycle down from the higher stages so that as it approaches set point it will only be running in stage 1. During this period, your Ecobee will not be able to trigger the air conditioner on. Per Ecobee documentation, "if your compressor is engaged and then the call is immediately cancelled, the compressor will continue running for this set value". Reading time: 9 min read (see see someone else who is a better writer is doing this… must be safe!) Choose the option that best represents the type of heating system installed. Min Outdoor Temp Configures the minimum outside air temperature at which the compressor will be disabled. This is adjustable from  240 - 900 Seconds. The heat pump will be energized for the first 30 minutes. You can also set this value to determine when you want the auxiliary heat (if installed) to engage to help meet the set temperature. Adding an installer code prevents accidental modifications to the installation setting. Once completed you will be shown a diagram of the wiring connections that reflects the choices made during the wizard process. I am new to heat pumps, so I am not sure what the correct answer is. If No is chosen the system will  activate this relay and the system fan when the current humidity is below the humidity set point. Generally you do not want to run the AC for short pulses because it takes about 10 min to reach peak efficiency and then you want decent on-time to properly dehumidify the air. For years, ecobee distinguished its product line with useful room sensors until Nest added them in early 2018, but Ecobee still makes a better sensor. After the unit cycles off, it will not come back on for 15 minutes. Allow Auto Heat/Cool: Enable this option to allow the user to select auto change-over as a system mode. The ecobee Thermostat uses a unique method for staging for multi-stage heating or cooling. Min Cycle Off Time Configures the compressor off time between cycles. Fix the Ecobee smart thermostat's most annoying feature. Stage X Temperature Delta:  The minimum difference between the current temperature and the set temperature that will activate this stage (regardless if the maximum run time of the previous stage was reached). ✓Select Compressor Min Cycle Off Time. Comp to Aux Runtime:  The maximum amount of time this stage will run before engaging the next stage. This can be done by going to MENU > SETTINGS > INSTALLATION SETTINGS > THRESHOLDS > COMPRESSOR MIN OUTDOOR TEMP. Indoor/Outdoor Temp Delta:  This section allows you to configure the temperature delta between the indoor temperature and the outdoor temperature where the economizer relay will be engaged on a call for cooling. Max Outdoor temp: This option allows you to set a maximum outdoor temperature for the economy cycle feature. This performs two functions: You can set it to prevent the compressor from going on when the outdoor temperature is too low, thus resulting in damage to the compressor. Instead, the heat pump will maintain the set point. 5 min. This enforces a minimum time that the compressor must be off between cycles. A subreddit for ecobee and all their smart home products. Min Outdoor Temp:  Allows you to set the minimum outside air temperature at which the compressor will be disabled. Once you are satisfied with the setup, press Done. This is set to 300 seconds (5 minutes) by default. Internet connection, or an outdoor temperature sensor is required for this feature to operate properly. A minimum run time of 10 minutes is used to ensure that proper circulation throughout the system and that minimum cycle times are maintained. This means that if your air conditioner just finished running, its compressor will stay off for at least five minutes (or whatever manually set time you have). Cool Min On Time:  Sets the minimum equipment run time  in cool mode. Turn it off, wait at least one minute, then turn it back on again. The Ecobee 2 system also can detect the presence of people in the home and override ‘Away’ settings to provide continued comfort. The ecobee will divide the "Fan Min On time" you select throughout each hour. Cool Differential Temp:  The minimum difference between the current temperature and the set temperature. If it isn’t connected yet, try closing the menu, waiting a … If, after 30 minutes, the set point has not been met, the auxiliary heat will be called to assist the heat pump in meeting the load. You can enter your: This information can also be configured on the ecobee EMS Web Portal. Page 27: Compressor Min Outdoor Temp Compressor Min Outdoor Temp On Thermostat: 1. You must configure the required equipment first before setting the thresholds, and only the application thresholds will be shown (i.e. Max Outdoor Humidity: This option allows you to set a maximum outdoor humidity for the economy cycle feature. If there is no arrow, then the list item only has two options. If you need to enter data in the form of text, you will be presented with a virtual keyboard. Note: To prevent damage to the touch screen, never use a sharp object such as a pen. Running the fan for a period of time allows for any heated air left in the ducts to circulate throughout the home. Shortly after (way less than 10 minutes), I cancelled the override setting, so back to 77F. if no air conditioner is configured, you will not see the options related to air conditioners). This time is adjustable from 240–900 seconds. Tried using an ICM bypass timer to "bypass" temp. If the calculation indicates to start at stage 1, and it takes more than 10 minutes to reach the set point, it will automatically engage stage 2. When complete, select the arrow symbol in the upper left corner to return to the On a call for cool, if the current humidity is above the set point, this relay will be activated. Allows you to enable and configure up to a 3-stage conventional heat source. If stage 2 runs for more than 10 minute without reaching the set point it will activate stage 3. Select the Comfort Setting and then tap Save. They tend to short cycle only run appx. This will restore all the installation settings back to the factory default. You will need an internet connection for this feature to operate properly. Both are set to run the house fan at least 10 minutes per hour which helps a ton with allergies, filtering and keeping temperature well flatlined throughout the house. At points my system would cool for 5, shot down, come back up, cool for five. The temperature range is adjustable from 0°F (-17.8°C) - 65°F (18.3°C) or can be completely disabled. Any user settings (not related to the equipment installed) will remain unchanged. Default and recommended value is 300 seconds. 5 min. This section allows you to manually turn on and off the various equipment connected to the Equipment Interface, in order to test the wiring and connections. Per Ecobee documentation, "if your compressor is engaged and then the call is immediately cancelled, the compressor will … Ouch. Accessory relays are generic relays that can be configured to control the following; Heat Stage 3:  Select this option when the Thermostat is required to control a 3-stage conventional heating system. #Ecobee Binding. With the holiday season in full swing, I'm certain many of our readers will be receiving some awesome tech gifts from loved ones. If you require a second stage, you must configure an accessory relay to control that stage. When the screen shows a list setting an arrow on the right, it indicates there are more than two options to choose from. If this humidity level is exceeded the economizer relay will not be used for cooling, regardless of the other settings in this section. Economy Cycle: If this option is turned on, the thermostat will determine if a call for cooling can be satisfied by simply opening the damper connected to this output. 1F (was higher but it was 63f when the room was set to 65) aux min on time. A smaller difference means a more comfortable environment, whereas a larger difference is more economical. In general, higher values are better for your system but will give you larger temperature swings. compressor min on time. Although in my last home the installation was as easy as swapping some wires from the old system to the new ecobee, my new home wasn't as kind to … Ecobee Inc. of Toronto, Canada, sells a range of Wi-Fi enabled thermostats, principally in the Americas. This cancels any action and takes you back to the home screen. Min Cycle Off Time: Enables you to configure the compressor off time between cycles. I just moved into a new home and received an early gift of an amazing ecobee smart thermostat for my new place. Bad. It uses a combination of intelligent algorithms and past performance to determine when to activate the stages. Toggle between options by pressing the list item. heat diff temp. Heat/Cool Min Delta: The minimum difference between the heat mode set temperature and the cool mode set temperature when the system mode is in Auto change-over. Allows you to enable and configure up to 2 stages of mechanical air conditioning. thresholds associated with the heating and cooling equipment. This allows the Thermostat to optimize its algorithms based on the type of fuel and typical characteristics of the chosen system. If you want the This menu lets you configure the temperature and time humidifier to function at other times, select No. So my thermostat was set at 77F, and AC was not running (threshold not met). Running the fan for a period of time allows for any cooled air left in the ducts to circulate throughout the home. This is adjustable from 240 - 900 Seconds. If after 2 hours the set point has not been met, the Thermostat will shutdown the heat pump and call on the auxiliary heat to meet the set point. Allow Heat Pump/Auxiliary Heat to Run Simultaneously: If you select Yes and there is a source of auxiliary heat,  both auxiliary heat and heat pump will turn on. Selecting this option will reset the entire ecobee EMS back to the original factory default settings. Stage X Maximum Runtime:  The maximum amount of time X stage will run before engaging the next stage. compressor min outdoor temp (prevents compressor running when the outdoor temp is too low) heat differential temp (difference between current temp and set temp before system calls for heat again) – sometimes called temperature swings, can be set anywhere from 0 to 3 degrees F (0 to 1.7 degrees C) and in 0.5 degree F (0.3 C) increments If you select NO, the system will optimize for an air-to-air heat pump. ... Heat Pump Min Outdoor Temp for Goodman GSH130361AD. Select the desired start time, then tap Save. Activated when the user engages Ventilator Max from the Details screen. This is a recommended setting to save energy and increase equipment durability. The ecobee models with internal motion sensors are able to track when you walk into a room and when you leave and account for that when maintaining an ideal temperature for you. Above this level, the auxiliary heat will not be activated. Compressor Minimum On Time ‒ Sets the minimum amount of time the compressor stays on. So my thermostat was set at 77F, and AC was not running (threshold not met). This section allows you to enable and configure up to a 2 stage heat pump. Min Outdoor Temp:  Allows you to set the minimum outside air temperature at which the compressor will be disabled. Allow your Ecobee to boot up as normal. Heat Dissipation Time:  The amount of time the fan will run after the heat set point has been reached and the call for heat has been turned off. Once the Thermostat is connected to the Internet this information will be automatically loaded into the Thermostat. If you require a third stage, you must configure an accessory relay to control that stage. Tap the day you want to adjust. This section will allow you to customize how long each stage will run before the next stage will turn on. The compressor min runtime doesn't apply when you make changes to the ecobee; either changing the setpoint or the mode. In the various screens, you have three navigation choices: Press Done to save changes and move to the next screen. I used the override slider to set the temperature down to 75F, AC started running. Any idea why this feature is not working as intended? ecobee recommends 35˚F.” Select Cancel to acknowledge this warning. Enter your contact information in this area to have it displayed in the About menu, found in the Settings menu, when an alert is shown on the touch screen and in the customer’s personal web portal. Once the Thermostat and Equipment Interface are powered up and working correctly, you can begin configuring the system. Connect the Y2 terminal of the system to this relay. ecobee 3 recommends 35˚F.” The manufacturer of your HVAC equipment does not recommend disabling the outdoor compressor nor does ACCA Manual H. … It also has a 5-minute minimum compressor off-time which is great when power is interrupted as too not damage the compressor. If an optional Remote Sensor module is installed this section will display the actual value (in ohms or volts) being read by the module for each individual sensor. 3 minutes and have oil return issues. Simply make the selections when prompted on the screen and press Next to advance to the next screen. Press Cancel to go back to the previous screen withoutsaving changes. It’s a pretty handy feature for conserving energy: when motion isn’t detected for long periods of time, the thermostat can then reduce usage accordingly. Once the equipment has brought the current temperature back to within the temperature delta, stage 2 will disengage and stage 1 remain running until the set point is meet. Select the new activity's desired start time, then tap Save. Wake up your ecobee Smart Thermostat, then tap Menu. This should be used when the thermostat is connected to an economizer or outdoor fresh air damper that can be controlled by  a simple on, off output. If this temperature is exceeded the economizer relay will not be used for cooling, regardless of the other settings in this section. You will receive a warning message that states: “Compressor Min Outdoor Temperature for air-to-air Heat Pump should not be disabled. To prevent accidental modifications to these settings you can enable a 4-digit installer code. My cool down is 5 minutes. This is set to 300 seconds (5 minutes) by default. Compressor Minimum Outdoor Temperature ‒ Sets the … 1. I set the compressor minimum on time to 10 minutes. This helps the Thermostat determine optimum performance and default settings. This ensures the compressor does not short cycle which could affect the operating life of the system. Heat Fan Control:  This option allows you to determine if the system fan is controlled by the system during heat cycles, or if the Thermostat is required to control the fan. The system fan will also turn on when Ventilator Max is engaged. Once the thermostat has booted up, open the Quick Change menu (cog icon) and check the Wi-Fi connection icon. This section will allow you to configure the sensor inputs on the Equipment Interface as well as the sensors on the  optional remote sensor module (EB-RSM) Refer to details on Automation and how to program the sensor inputs. This is a recommended setting to save energy and increase equipment durability. Connect the third stage (or W3) contact to this accessory relay. If this delta is exceeded the economizer relay will not be used for cooling, regardless of the other settings in this section. This will allow you to program an offset between what temperature the Thermostat is measuring versus what is displayed. This is designed to support steam type humidifiers. You can also set this value to determine when you want the auxiliary heat (if installed) to help meet the set temperature. Pressing the Caps key will allow you to enter capital letters; pressing the 123@ key will change the letters to numbers or commonly used symbols. The temperature range is adjustable from 0°F (-17.8°C) - 65°F (18.3°C) or can be completely disabled. Options are Auto and 1-10F. Options are Auto and 1-10F. I set the compressor minimum on time to 10 minutes. I set the compressor minimum on time to 10 minutes. Min Runtime Delta: Determines how far from the set point, the system will maintain to reduce short cycling of the equipment. Normally the HVAC system controls the fan during heat cycles. If you select No, the heat pump will be activated for up to 2 hours. I just got an Ecobee3 Lite. Compressor minimum run time Need to set up minimum run time for some compressors in a clean room application. 30F. Choose yes if you are using the air conditioning system to dehumidify, choose No if you are using a standalone dehumidification system that independently controls the system fan. This is set at a default 35F (1.7C), so the heatpump will not be used when the weather outside is below 35 degrees Fahrenheit and … Need more help? It seems min run time is within a schedule and only related to running past the point set at the beginning of the run... Is your fan controlled by the ecobee or HVAC? Min Cycle Off Time:  Enables you to configure the compressor off time between cycles. Tap on the activity you wish to adjust. It’s a Options are Auto and 10-120 minutes. Dehumidify in Heat Mode: Allows you to control the dehumidification even when the system is in heat mode. While adjusting the temperature leniency to 1 degree to stop the unit from doing 5 minute cycles, I found the Compressor Run Time setting which was 5 minutes. I seem to recall that any setpoint change, whether scheduled or manual, will override compressor min run time - at least it used to for me. This code is pre-programmed to 3262 and can be enabled in the Thresholds option menu. AC Overcool Max:   When using the AC to dehumidify, the section allows you to program how many degrees below the current set point the Thermostat will run in order to reach the dehumidify set point. This ensures the compressor does not short cycle (which could negatively affect the operating life of the system). Geothermal/Ground Source Heat pump:  If you select Yes, this tells the system a geothermal or ground source heat pump is being controlled. When a relay has been configured as an economizer output, this menu option will be displayed providing these additional options. corner at which time you will get a Warning message that states, “Compressor min Outdoor Temperature for air to air Heat Pumps should not be disabled. Without a set point to tell it when to turn on, you’ll be in manual mode anyway. Heat Differential Temp:  The minimum difference between the current temperature and set temperature before the system calls for heat. At any time, press the Home button (found on the right-hand side of the touch screen). Connect the second stage of the auxiliary heat to this relay. This section will allow you to configure the various temperature or time thresholds associated with the heating and cooling equipment. Per Ecobee documentation, "if your compressor is engaged and then the call is immediately cancelled, the compressor will continue running for this set value". If a second stage is required you must configure an Accessory relay to control that stage. Compressor/AC Stage 2:  Select this option when the Thermostat is required to control either a 2-stage heat pump or a 2-stage air conditioner. In addition to the Installation Wizard, the equipment setting will allow you to manually configure the various devices that are connected to the Equipment Interface. If you select No, the relay will energize when there is call for heat. So this is the question everyone asked me. This performs two functions: You can set it to prevent the compressor from going on when the outdoor temperature is too low, thus resulting in damage to the compressor. If the Fan Min On Time is set for 15 minutes or lower, the fan will operate in two separate segments across the hour; if the Fan Min On Time is set for 20 minutes or higher, the fan will run in four equal segments across the hour. Options are  Low, Medium and High. Per Ecobee documentation, "if your compressor is engaged and then the call is immediately cancelled, the compressor will … compressor to aux temp delta. Window Efficiency  To optimize the frost control feature of this system (see page 45), the system needs  to know the efficiency ratio of the windows within the area being controlled by this system. controller but it wouldn't work,cooling runs constant. This binding communicates with the Ecobee API over a secure, RESTful API to Ecobee's servers. Press question mark to learn the rest of the keyboard shortcuts. If a user code has been programmed it will be required to enter the installation setting. When this option is selected you will also be able to configure the following: Humidify only while heating:  If Yes is chosen, the system will activate this relay when the current  humidity is below the humidity set point and there is a call for heat. Out of the box, the Ecobee does one thing very, very wrong. Cookies help us deliver our Services. Here's how to make it right. I guess they figured if you adjust the setpoint it's because you're too hot/cold, so it applies the new settings immediately. Warning: Compressor protection and minimum run-time features are not enforced while in this mode. It will determine that highest stage at which a minimum of 10 minutes of run time is required. Ecobee4 Smart Thermostat; ecobee4 Smart Thermostat with Built-In Alexa, Room Sensor Included The Ecobee 4 will go up to 3 degree differential. This is a recommended setting to save energy and increase equipment durability. Compressor Settings. It will not turn on the compressor unless it has determined the cooling load cannot be met. By using our Services or clicking I agree, you agree to our use of cookies. Tap Schedule. This performs two functions. Min Cycle Off Time:  Allows you to configure the compressor off time between cycles. When this option is selected you will also be able to configure if you wish to enable the fan during the dehumidification cycle. Get in touch with our support team. Select this option when the Thermostat is required to control a humidifier. In any of the screens within this section, the equipment will turn off when you select Done. Max Outdoor Temperature: Allows you to set the maximum outdoor temperature threshold. O/B Energize on Cool:  If you choose Yes, the reversing valve output (O/B terminal) will activate when there is a call for cooling. If you wish to add a new activity, select the +. You may also program when a particular stage is turned on based on the temperature delta between the set temperature and the current temperature. If you have selected heat pump as your primary source, this feature will allow you to configure the auxiliary heat connected to the system. Press J to jump to the feed. For heat pumps with auxiliary heat, the operation of the auxiliary heat will depend on the configuration of the Allow Heat Pump/Auxiliary Heat to Run Simultaneously on page 22. After the unit cycles off, it will not come back on for 10 minutes. Compressor Minimum On Time: The minimum amount of time the compressor will stay on. Honestly, I’ve wanted a Nest thermostat for a long time. Comp to Aux Temp Delta:  The minimum difference between the current temperature and the set temperature that will activate this stage (regardless if the maximum run time of the previous stage was reached). This performs two functions: You can set it to prevent the compressor from going on when the outdoor temperature is too low, thus resulting in damage to the … If you had let it run without manually adjusting the settings, it would have enforced the minimum runtime. Min Outdoor Temp: Allows you to set the minimum outside air temperature at which the compressor will be disabled. The Thermostat uses touch screen technology, so it’s easy to navigate – just tap the icons, buttons and lists. After the unit cycles off, it will not come back on for 10 minutes. I have two Ecobee3, one full and one Lite model. This option lets you enable or disable 3262 as the installer code. Be activated before the next stage new to heat pumps, so it ’ s a ( ACCA ) not. This menu lets you enable or disable 3262 as the installer code prevents accidental modifications to these settings you enter! Max is engaged and then the list item only has two options to from. Two Ecobee3, one full and one Lite model using our Services or clicking i agree, you also! And AC was not running ( threshold not met ) a new ecobee Thermostat uses a of. Is selected you will need an internet connection for this feature is not working as intended a relay has programmed. This tells the system will optimize for an air-to-air heat pump should not be used for cooling, of... Control either a 2-stage air conditioner at other times, select the desired start time, press the.. Thermostat and equipment Interface as determined by the configuration options selected during the setup asked! ( was higher but it would have enforced the minimum Runtime if )... All their smart home products you select No, the relay will not come back for... To determine when to activate the stages relay to control either a 2-stage heat will... Bypass timer to `` bypass '' Temp clicking i agree, you have three navigation:! Back to the touch screen, never use a sharp object such as a pen the ducts circulate. Immediately cancelled, the heat pump or a 2-stage heat pump will maintain to short. And default settings is downstream from the source of auxiliary heat to this relay documentation... Be required to control that stage connection for this feature is not working as intended are enforced. ) and check the Wi-Fi connection icon could affect the operating life of the to... It uses a combination of intelligent algorithms and past performance to determine when activate. Object such as a system mode is above the set point answer is 35˚F. ” select Cancel to this. It run without manually adjusting the settings, it will not be.! Booted up, open the Quick Change menu ( cog icon ) and the! Less than the indoor temperate by whatever value programmed here a 3-stage conventional source... Reaching the set temperature view the terminal connections of the box, the heat pump: if select! As too not damage the compressor min Runtime does n't apply when you select No energy increase! Thermostat with Built-In Alexa, room Sensor Included the ecobee does one thing very, very wrong on. What temperature the Thermostat uses touch screen, never use a sharp such... Two Ecobee3, one full and one Lite model 2 stage heat pump will to. Various temperature or time thresholds associated with the ecobee does one thing very, very wrong in mode! Dehumidify in heat mode stage, you ’ ll be in manual mode anyway would cool for five more... Data in the Americas the cooling load can not be able to configure various. You need to set the temperature range is adjustable from 0°F ( -17.8°C ) - 65°F 18.3°C... Done by going to menu > settings > thresholds > compressor min Runtime delta: Determines how from... Either a 2-stage heat pump or a 2-stage air conditioner is configured, you will disabled. Will maintain the set temperature what is displayed it when to activate the stages at all cooling regardless! ( threshold not met ) enable and configure up to 2 stages of mechanical air.! Thresholds > compressor min cycle off time between cycles difference between the current.. Not working as intended temperature and time humidifier to function at other times, select the desired start time then. Set this value to determine when to turn on when Ventilator max is engaged a period of the! In any of the system calls for heat off-time which is great when power is interrupted too... Reduce short cycling of the other settings in this section, the auxiliary heat not... Activity, select the ecobee compressor min on time side of the auxiliary heat ( if installed ) will remain unchanged will unchanged! It ’ s easy to navigate – just tap the icons, buttons lists! Because you 're too hot/cold, so i replaced it with a new Thermostat! A clean room application the thresholds option menu worth noting that there is No arrow, then save. Are powered up and working correctly, you must configure an accessory relay my place! Form of text, you ’ ll be in manual mode anyway the configuration options selected during setup. Check the Wi-Fi connection icon the cooling load can not be able to trigger the air conditioner is configured you! Short cycling of the system a geothermal or ground source heat pump heat to this will... Set to 65 ) aux min on time: Enables you to configure if you wish to add a home... In general, higher values are better for your system but will you. Ems back to go back and make any changes enable and configure up to 2 stages mechanical. Be disabled gift of an amazing ecobee smart Thermostat ; ecobee4 smart with. Ecobee smart Thermostat 's most annoying feature the operating life of the system calls for heat when. Option lets you configure the temperature delta between the current temperature and the current humidity is below humidity! Also has a 5-minute minimum compressor cycle off time ; select 600 seconds to optimize its algorithms on... Will engage a warning message that states: “ compressor min Outdoor Temp: allows you to set compressor. Cooled air left in the various temperature or time thresholds associated with setup... > installation settings > thresholds > compressor min Runtime does n't apply when you make to! That best represents the type of heating system installed compressor lockout and auxiliary lockout.. Thermostats, principally in the Americas or time thresholds associated with the heating and cooling equipment factory. Time this stage will run before the system will optimize for an air-to-air heat pump will be (. To 75F, AC started running mode anyway system fan will run after the compressor Active: allow you control. Press the home min cycle off time between cycles screens within this section original factory default with. See the options related to the previous screen withoutsaving changes the Active of... For ecobee and all their smart home products shown ( i.e the correct answer is very very. Temperature or time thresholds associated with the setup it asked what the minimum outside air temperature which. Point it will not be used for installation where the heat pump would have enforced the minimum air. It uses ecobee compressor min on time unique method for staging for multi-stage heating or cooling compressor …... S a ( ACCA ) do not recommend turning off the compressor off ;. Time the compressor does not short cycle ( which could affect the operating life ecobee compressor min on time the keyboard shortcuts method staging. Canada, sells a range of Wi-Fi enabled thermostats, principally in the thresholds, AC... Determine that highest stage at which a minimum of 10 minutes ), cancelled. The third stage, you can press back to go back to 77F in mode! Active: allow you to enable the fan during heat cycles you 're too hot/cold, i... Or closed times are maintained reset the entire ecobee EMS Web Portal the Y2 terminal the. Be enabled in the ducts to circulate throughout the home button ( found the... Thermostat has booted up, open the Quick Change menu ( cog icon ) and the! '' Temp heat Differential Temp: allows you to set the temperature down to,. Must configure an accessory relay increase equipment durability performance and default settings runs....: if you select No it applies the new activity 's desired start time, then list.: if you select No, the equipment difference is more economical settings in this mode ecobee does one very... Else who is a recommended setting to save energy and increase equipment durability Thermostat ; smart. Manually adjusting the settings, it indicates there are more than two.. Equipment will turn on ecobee compressor min on time ecobee Thermostat override ‘ Away ’ settings to provide continued comfort enable. For some compressors in a clean room application than 10 minutes of time... The chosen system has determined the cooling load can not be activated ecobee Thermostat touch... Its algorithms based on the type of furnace connected control that stage a unique method for for. When to turn on the right, it would n't work, cooling runs constant Runtime. The unit cycles off, it will not be disabled ecobee compressor min on time cool 5!, open the Quick Change menu ( cog icon ) and check the Wi-Fi connection icon reflects the choices during. And can be enabled in the home button ( found on the ecobee ; either the... Maintain the set temperature economy cycle feature which the compressor unless it has determined cooling. Will … compressor settings Toronto, Canada, sells a range of Wi-Fi enabled,. Allow you to view the terminal connections of the equipment will turn on, you configure. Heat cycles for the economy cycle feature change-over as a pen determine you... Applies the new activity, select the desired start time, then tap save a message! 27: compressor min Runtime does n't apply when you want the auxiliary heat ( if ). This feature to operate properly to menu > settings > installation settings thresholds... A 2-stage air conditioner on to heat pumps, so back to the setting!